Programming and Parameters 3-33
Advanced Program Group (continued)
A098 [SW Current Trip] Related Parameter(s): P033
Enables/disables a software instantaneous (within 100 ms) current trip.
Values Default: 0.0 (Disabled)
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
A099 [Process Factor] Related Parameter(s): b010
Scales the output frequency value displayed by b010 [Process Display].
Values Default: 30.0
Min/Max: 0.1/999.9
Display: 0.1
Output
Freq
Process
Factor
Process
Display
=
x
A100 [Fault Clear]
Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options 0 “Ready/Idle” (Default)
1 “Reset Fault”
2 “Clear Buffer” (Parameters b007
-b009 and d310-d316 [Fault x Code])
A101 [Program Lock]
Protects parameters against change by unauthorized personnel with a 4-digit password.
Options 0 “Unlocked” (Default)
1 “Locked”
A102 [Testpoint Sel] Related Parameter(s): b019
Used by Rockwell Automation field service personnel.
Values Default: 400
Min/Max: 400/FFFF
Display: 1 Hex