PowerFlex® 70 Adjustable Frequency AC Drive Installation Instructions 47
Manually Clearing Faults
Step Key(s)
1. Press Esc to acknowledge the fault. The fault information will be
removed so that you can use the Human Interface Module (HIM).
2. Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.
3. After corrective action has been taken, clear the fault by one of
these methods:
• Press Stop
• Cycle drive power
• Set parameter 240 [Fault Clear] to “1.”
• “Clear Faults” on the Human Interface Module (HIM) Diagnostic
menu.
Esc