34 Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017
Chapter 2 Configure the Interface
Using the PowerFlex 20-HIM-A6 or 20-HIM-C6S to Access
Parameters
If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM,
it can be used to access parameters in the interface.
1. Display the Status screen, which is shown on HIM power-up.
2. Use the or key to scroll to the Port 0 where the built-in
EtherNet/IP interface resides.
3. To display the Jump to Param # entry popup box, press the PAR# soft key.
4. Use the numeric keys to enter the desired parameter number, or use the
▲ or ▼ softkey to scroll to the desired parameter number.
For details on how to view and edit parameters, see the
PowerFlex 20-HIM-A6/-C6S HIM (Human Interface Module) User Manual,
publication 20HIM-UM001
.
Change the Source for the Network Address
1. Verify that the IP address switches (Figure on page 28) are set to 999.
2. Set the value of 0:300 - [Net Addr Sel] to ‘1’ (Parameters).
3. Reset the interface by cycling power to the drive or by using the HIM
Reset Device function that is located in the DIAGNOSTIC folder of
the drive.
4. Set the IP address, subnet mask, and gateway address by using interface
parameters. Perform the steps in the following subsections.
Value Setting
1 Parameters
2BOOTP
3 DHCP (default)