14 1791 99914
Zone Type
Zone Attributes
Key Zones
CS350 Programming Functions
TYPE FUNCTION
. Exit/Entry Input is bypassed during exit time when arming the
system. If after the exit time the zone is still open, the
panel will not arm and act as programmed in
function 6.1.5. During the entry procedure the entry
timeris started which allows disarming.
output : buzzer, alarm, interior bell, exterior bell, fire
reset
. Alarm Input is only active when the system is armed and
it will act according to its programmed attributes.
outputs : alarm, interior bell, exterior bell, system
clear, fire reset
. Keypad Lockopening this input will disable access to the keypad.
. Key Infinite creates an infinite exit time. Only after opening and
closing this zone will the panel arm after four
seconds. Re-activation starts an infinite entry time.
. Exit The exit time stops and system arms 4 seconds
after Terminator closing the input.
4.2 Zone Attributes
Attributes define the operation of the zone type. Some types
have attributes inherent to them. Others can not be changed
which will be displayed by [No Option].
ATTRIBUTE FUNCTION
. In Allows inhibiting of alarm and exit/entry zones
. 24 Creates a 24Hrs zone. Only applicable for Alarm types.
. Pg Partguard. Zone is inhibited during partguard protection.
. So Soak Test. The related input will not activate any alarm output
but only log its events.
. Ac Access zone. Follows the exit/entry input. Will create a direct
alarm when triggered prior to the exit/entry input, except if pro-
grammed for Access/EE and the panel is in Partguard mode (see function
6.3.2.).
. Ch Chime. Input activates buzzer/ interior bell when in disarmed
state.
. Ls Local Shock. Shock sensor alarm triggers 'perimeter' output
instead of 'alarm' output. See also Peridiax programming on p.19.
. La Local Alarm. Both shock sensor and/or contact activation will
trigger the perimeter output. See also Peridiax programming on p.19.