Bells do not ring at 1. Check bell fuse.
bell test. 2. Disconnect bell cable from control panel and connect across battery
observing correct polarity. If wiring is correct the bell should ring.
Alarm zone does not Arm system and remove wires from the terminal block. If the system does
activate system. not activate, disarm and enter Engineer Mode.
1. Check if bell delay time is programmed for [00] ('Timers Menu' at 'Bell
Times').
2. Check if zone is not in soak test ('Zones Menu' at 'Zone Attributes').
3. If PA zone, check that it is programmed as audible ('Miscellaneous Menu'
at 'PA Menu').
Alarm zone name will 1. Enter Engineer mode and open panel.
not clear from the 2. Disconnect the alarm zone wires from the terminal block and replace with
display when attempt- a 4K7 resistor.
ing to arm the system. 3. Enter 'Show Open Zones' in 'Maintenance Menu' and observe that the
zone name in question does not come up on the display. This proves
that the panel is functioning correctly.
4. Check the zone wiring to ensure that the circuit is closed and that there
are no shorts on the cables. Reconnect the wires back to the panel and
retest.
Control panel activates 1. Check that the battery is connected correctly.
during a short power 2. Check that the battery fuse is not blown.
failure. 3. Ensure that the battery is fully charged and is large enough to carry the
load of the system.
System returns to Check that jumper is on link LK1 on the main control panel.
factory setting when
mains and battery
powre are removed.
System activates Before leaving engineer mode check that no PA, FIre, Medical, or Tamper
when leaving engineer zones are open. Use 'Show Open Zones' menu to do this.
mode.
System does not
activate when Tamper
opens during day
(ie when system is
disarmed).
Problem Solving
Check that the internal sounder is connected.
NOTE: the external bell only sounds on tamper fault when the system is
armed. If using dual loops, check that the zone type is programmed for
DUAL (in 'Zones' menu) and that the Tamper devices are wired in series with
the EOL resistor.