EasyManuals Logo

Baxi luna duo-tec MP+ 1.35 User Manual

Baxi luna duo-tec MP+ 1.35
Go to English
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
31
INSTALLER Section (en)
7221369.01 (1-03/15)
10. INSTALLING THE FLUE
The boiler is easy and exible to install thanks to the extensive range of available
accessories, as described below. The boiler has been designed for connection to a
vertical or horizontal coaxial ue-air duct. The boiler can also be used with separate
ducts using the accessory splitting kit.
WARNINGS
C13, C33 The terminals for separate ues must be tted inside a 50 cm square. Detailed
instructions are provided with the individual accessories.
C53 Do not t the ue and air duct terminals on opposite walls of the building.
C63 The maximum pressure drop ΔP of the ducts must not exceed the values indicated
in table 1A. The ducts must be certied for this specic use and for a temperature in
excess of 100°C. The ue terminal must be certied to EN 1856-1.
C43, C83 The ue terminal or ue duct must be suitable for the purpose.
For optimal installation, the accessories supplied by the manufacturer should
be used.
TABLE 1A
If the ue and air ducts installed are not supplied by our company, make sure they
are certied for the type of use and have a maximum pressure drop as indicated in
the table to the side.
∆P (Pa)
1.35 MP 160
1.50 MP - 1.60 MP - 1.70 MP 270
To optimise operating safety, make sure the ue ducts are rmly xed to the wall with suitable brackets. The brackets must be
positioned over the joints at a distance of approximately 1 metre from one another.
Make sure there is a minimum downward slope of 5 cm per metre of duct towards the boiler.
SOME OUTLET DUCT INSTALLATION EXAMPLES AND THEIR RELATIVE MAXIMUM LENGTHS ARE SHOWN IN ANNEX
"SECTION" D AT THE END OF THIS MANUAL.
10.1 CONCENTRIC DUCTS
This type of duct is used to discharge exhaust fumes and draw
combustion air both outside the building and if a LAS ue is
tted. The 90° coaxial bend allows the boiler to be connected
to a ue-air duct in any direction as it can be rotated by 360° It
can also be used as a supplementary curve combined with a
coaxial duct or a 45° curve.
If fumes are discharged outside the building, the ue-air
duct must protrude at least 18 mm from the wall to allow an
aluminium weathering surround to be tted and sealed to
avoid water inltrations.
A 90° bend reduces the total duct length by 1 metre.
A 45° bend reduces the total duct length by 0.5 metres.
The rst 90° bend is not included when calculating the maximum available length.
10.2 SEPARATE DUCTS
This type of installation makes it possible to discharge exhaust
fumes both outside the building and into single ue ducts.
Comburent air can be drawn in at a different location from that
of the ue terminal. The accessory splitting kit comprises a ue
duct adaptor (80) (B) and an air duct adaptor (A). For the air
duct adaptor, t the screws and seals previously removed from
the cap.
The 90° bend is used to connect the boiler to the inlet and
outlet ducts, adapting them to various requirements. It can also
be used as a supplementary curve combined with a duct or a
45° bend.
A 90° bend reduces the total duct length by 0.5 metres.
A 45° bend reduces the total duct length by 0.25 metres.
The rst 90° bend is not included when calculating the maximum available length.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baxi luna duo-tec MP+ 1.35 and is the answer not in the manual?

Baxi luna duo-tec MP+ 1.35 Specifications

General IconGeneral
BrandBaxi
Modelluna duo-tec MP+ 1.35
CategoryBoiler
LanguageEnglish

Related product manuals