INSTALLER Section (en)
7221369.01 (1-03/15)
14. PARAMETERS SETTING
To programme the parameters of the boiler electronic board, proceed as follows:
Press together and hold them down for 6 seconds until programme row “P02” appears on the display alternated with
the set value (°C);
Press
and hold down for 6 seconds until "On" appears on the display. Release the button and "P01" appears on the display;
Press
to scroll the list of parameters;
Press
, the value of the selected begins ashing, press to change the value;
press
to conrm the value or press to exit without saving.
Further information concerning the parameters listed in the following table are supplied together with the required
accessories.
(a) (b) ZONE 1 HEATING PARAMETERS (main zone)
Factory
setting
Minimum Maximum
P01 700 *Operating mode (0=Frost Protection, 1=Timed, 3=T.comfort) - 3 0 3
P02 712 *Reduced ambient temperature °C 16 4 35
P03 720 *“Kt” curve slope - 1,5 0,1 4
P04 721 *“Kt” curve drift - 0 - 4,5 4,5
P05 726 *“Kt” curve adaptation (0=off) - 1 0 1
P06 740 Flow temperature setpoint (minimum value) °C 25 8 80
P07 741 Flow temperature setpoint (maximum value) °C 80 25 80
P08 742 *Enable modulating temperature if set = “---” °C 80 25 80
P09 750 *Room inuence (“---” = disabled) % 50 1 100
P10 834 *Opening/Closing speed of mix valve S 30 30 873
ZONE2 HEATING PARAMETERS (with accessory Expansion Unit)
P11 1000 *Operating mode (0= Frost Protection, 1=Timed, 3=T.comfort) °C 3 0 3
P12 1010 *Comfort room temperature °C 20 4 35
P13 1012 *Reduced room temperature °C 16 4 35
P14 1020 *“Kt” curve slope - 1,5 0,1 4
P15 1021 *“Kt” curve drift - 0 - 4,5 4,5
P16 1026 *“Kt” curve adaptation (0=off) - 1 0 1
P17 1040 Flow temperature setpoint (minimum value) °C 25 8 80
P18 1041 Flow temperature setpoint (maximum value) °C 80 25 80
P19 1042 *Enable modulating temperature if set = “---” (ow temp. setpoint if P63=0) °C 80 25 80
P20 1050 *Room inuence (“---” = disabled) % 50 1 100
P21 1134 *Opening/Closing speed of mix valve s 30 30 873
DHW PARAMETERS
P22 1620
Operating mode in DHW (with Remote Control)
- 2 0 20=always enabled, 1=according to hourly heating programme,
2= according to hourly DHW programme.
P23 1640
Anti-legionella function Disabled
- 0 0 1
0=disabled, 1=periodic (depending on P24)
P24 1641
Periodic anti-legionella function enable (only if P23 =1)
- 7 1 7
1=daily, 2..6=intervals of 2..6 days, 7=once a week
P25 1663 Circulation temperature setpoint (additional DHW pump) °C 45 8 80
P26 5470 Preheating time for DHW circuit (1=10’ -- 144=1440’) min 0 0 144
BOILER PARAMETERS
P27 2243 Minimum boiler off time min 3 0 20
P28 2217 Frost Protection setpoint °C 5 -20 20
P29 2250 Pump post-circulation time min 3 0 240
P30 2441 Max. fan speed (heating) rpm xxx 0 8000
P31 2455 Minimum boiler off differential °C 5 0 20
P32 2720 Not used (Do NOT change this parameter) - 0 0 1
P33 2721 Not used (Do NOT change this parameter) - 1 1 2
SOLAR PLANT PARAMETERS (with accessory Expansion Unit)
P34 3810 Temperature - on differential °C 8 0 40
P35 3811 Temperature - off differential °C 4 0 40
P36 3830 Pump start function (“---” = disabled) min --- 5 60
P37 3850 Solar panel manifold overheating protection (“---“ = disabled) °C --- 30 350
P38 5050 DHW boiler tank charging temperature max °C 65 8 95
P39 5051 Maximum temperature of storage tank °C 90 8 95

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baxi luna duo-tec MP+ 1.35 and is the answer not in the manual?

Baxi luna duo-tec MP+ 1.35 Specifications

General IconGeneral
BrandBaxi
Modelluna duo-tec MP+ 1.35
CategoryBoiler
LanguageEnglish

Related product manuals