EasyManuals Logo

Carrier 50PG20 User Manual

Carrier 50PG20
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
42
Two methods are used to add and remove stages of cooling
for units with more than one compressor. The first method
causes the unit to operate around its steady-state number of
stages. For example, if the correct number of stages is between
0 and 1, this method will cause the first stage to cycle. If the
correct number of stages is between 1 and 2, this method will
cause the second stage to cycle. The second method causes the
unit to find the steady-state number of stages. Details of these
methods are provided below.
The control uses two methods to add a stage of compressor
cooling. The first method will add a stage of cooling when the
Cooling Demand (Operating Modes
COOL
SPT
DMD.C) plus the change in cool demand (Operating
Modes
COOL
SPT
TRD.C) times the Cool Thermal Lag
Factor (Operating Modes
COOL
SPT
C.LAG) is greater
than the SPT Cool Demand (+) Level (Operating Modes
COOL
SPT
CL.PD).
DMD.C + TRD.C * C.LAG > CL.PD
This method is only used after the Compressor Settling
Time (Configuration
UNIT
SAT.T), has been exceeded
and the supply-air temperature is slowly increasing. The sec-
ond method will add a stage of cooling when Cool Demand is
greater than the SPT Cool Demand (+) Level plus 0.5° F
(DMD.C > CL.PD + 0.5) and the supply-air temperature
(Operating Modes
COOL
SAT
SAT) is changing at a
rate greater than –0.3° F per minute.
The control uses two methods to remove a stage of com-
pressor cooling. The first method will remove a stage of cool-
ing when the Cooling Demand (Operating Modes
COOL
SPT
DMD.C) plus the change in cool demand (Operating
Modes
COOL
SPT
TRD.C) times the Cool Thermal Lag
Factor (Operating Modes
COOL
SPT
C.LAG) is less
than the SPT Cool Demand (–) Level (Operating Modes
COOL
SPT
CL.ND).
DMD.C + TRD.C * C.LAG < CL.ND
This method is only used after the Compressor Settling
Time (SAT.T), has been exceeded and the supply air tempera-
ture is slowly decreasing. The second method will remove a
stage of cooling when Cool Demand is less than the SPT Cool
Demand (–) Level minus 0.5° F (DMD.C < CL.ND – 0.5) and
the supply air temperature (SAT) is changing at a rate less than
0.2° F per minute.
Configurable delays also apply when adding stages
(Configuration
COOL
C.INC) or removing stages
(Configuration
COOL
C.DEC). Compressor minimum
on-time (Configuration
COOL
MRT.C) and minimum
off-time (Configuration
COOL
MOT.C) also apply.
OUTDOOR FANS Each unit has a means for variable
outdoor airflow to control condenser pressure control within an
acceptable range by responding to varied operating modes and
ambient temperatures. This is implemented differently on
different units using multi-speed motors, multiple outdoor fans,
or variable-speed motor controllers.
NOTE: Factory default configurations account for these model
differences and should not be changed. The default configura-
tions have been qualified over a large range of conditions and
are provided in case a field replacement of a control board
occurs and the settings need to be checked or manually config-
ured. Outdoor fan operation is further described below to assist
in troubleshooting.
Units Without Humidi-MiZer™ System
— The outdoor fan
speed, number, and location for each of three levels is defined
for each cooling circuit in the Circuit submenus (Configura-
tion
COOL
CIR.x). Results of the factory configurations
are shown in Tables 38A-39B. The fan level selected during
operation is based on factory configurations of outdoor
temperature limits and condenser pressure limits. These are in
the Outdoor Fan Control submenu (Configuration
COOL
OFC). Initial fan level starts at zero and increments to
level 1 when Fan LEV0 Max Pressure limit is reached. Chang-
es between levels 1 to 3 are initially selected based on outdoor
air temperature (OAT) input and the level On and Off tempera-
ture limits. The levels may be further adjusted based on the
circuit saturated condensing temperatures (Temper a-
tures
REF.T
SCT.x) and the level Max and Min pressure
limits.
Units With Humidi-MiZer System
— Outdoor fan control for
Humidi-MiZer units includes a Motormaster® variable-speed
control for OFM1 and OFM4. Contactor OFC1 controls power
to the Motormaster control. The Motormaster control automat-
ically adjusts the outdoor fan speed to maintain approximately
80 to 100 F condenser temperature for circuit A at all outdoor
ambient temperatures. Contactor OFC2 controls the remaining
two fans (48/50PG20) or remaining 4 fans (48/50PG24 and
28). The fan level operation is determined by some or all out-
door fan control configurations described above, plus addition-
al Humidimizer configurations (Configuration
HZMR).
Table 38A — Outdoor Fan Level Transitions
without Humidi-MiZer System
Table 38B — Outdoor Fan Level Transitions
with Humidi-Mizer System
Table 39A — Fan Level Control of Outdoor Fan
Contactors (1, 2, 3) without Humidi-MiZer System
Table 39B — Fan Level Control of Outdoor Fan
Contactors (1 and 2) with Humidi-Mizer System
Gas Heating (48PG Units) — For 48PG units, the
heat type configuration Configuration
HEAT
HT.TY will
be factory set to a value of 1.
Heat will not operate if the outdoor temperature is
greater than the value configured for the heat lockout tempera-
ture, Configuration
HEAT
HT.LO. Minimum on-time,
Configuration
HEAT
MRT.H, and minimum off-time,
Configuration
HEAT
MOT.H, timeguards apply to both
stages of heating. Factory default values are 2 minutes On and
2 minutes Off. The IGC minimum on-time of 1 minute will be
followed even if MRT.H is lower and during Service Test.
FAN LEVEL OUTDOOR TEMPERATURE (F)
Level 2 On 55 (size 20), 45 (sizes 24, 28)
Level 2 Off 50 (size 20), 40 (sizes 24, 28)
Level 3 On 65
Level 3 Off 55
FAN LEVEL OUTDOOR TEMPERATURE (F)
Level 2 On 68 (size 20), 61 (size 24 and 28)
Level 2 Off 57
Level 3 On 88 (size 20), 68 (size 24 and 28)
Level 3 Off 78 (size 20), 62 (size 24 and 28)
FAN LEVEL
CIRCUIT
AB
0 ——
1
1 (20, 24)
1, 3 (28)
3
2
1, 2 (20)
2 (24, 28)
2, 3(20)
2 (24, 28)
3 1, 2 (20, 24) 1, 2, 3 (28) 2, 3
FAN LEVEL CIRCUITS A and B
0
1 1
2
1, 2 (20)
2 (24-28)
3 1, 2

Table of Contents

Other manuals for Carrier 50PG20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 50PG20 and is the answer not in the manual?

Carrier 50PG20 Specifications

General IconGeneral
BrandCarrier
Model50PG20
CategoryAir Conditioner
LanguageEnglish

Related product manuals