EasyManuals Logo

Carrier Aquasnap 30RB 160R User Manual

Carrier Aquasnap 30RB 160R
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
Refer to the diagram in the "Hydraulic connections" section for
all references points mentioned in this chapter.
The water circulation pumps for the units in the range have been
sized to allow the hydraulic modules to operate in all possible
congurations  based  on  the  operating  conditions  specic  to  the 
system, i.e. at a range of temperature di󰀨erences between the water
inlet and outlet (Delta T) at full load which may vary from 3 to 10 K.
This temperature  di󰀨erence  required  between  the  water  inlet  and
outlet  determines  the  nominal  ow  rate  of  the  system.  Use  the 
specication  provided  when  selecting  the  unit  to  determine  the 
system's operating conditions.
In particular, take down the data to be used for the control of the
system ow rate:
Units without hydraulic module: the rated unit pressure drop.
This is measured with pressure gauges that must be installed
at the inlet and outlet of the unit (item 21).
Units with xed speed pumps: nominal ow rate. The pressure
of the uid is measured by sensors installed at the inlet of the
pump and outlet of the unit (items 7 and 10). The controllers
then  calculate  the  ow  rate  associated  with  this  pressure 
di󰀨erence and display the result on the user interface. (refer 
to the unit control manual).
Units with variable speed pumps: regulation of the constant
pressure di󰀨erential based on readings at the hydraulic module
inlet and  outlet. The water  bu󰀨er tank  module option is not 
taken into account.
Units with variable speed pumps: regulation of the temperature
di󰀨erence measured at the heat exchanger inlet and outlet.
If this information is not available when the system is commissioned,
contact the engineering and design department responsible for the
system to obtain it.
This data can be obtained either from the performance tables included
in the technical documentation (for cases where the evaporator
temperature delta is 5 K) or from the "Electronic Catalogue" selection
program for all other applicable temperature delta in the range of 3 to
10 K.
8.3 - Units without hydraulic module
8.3.1 - General information
The nominal ow of the unit will be set using a manual valve that
should be installed on the outlet of the unit (item 19 on the schematic
hydraulic circuit). Changing the pressure drop of the valve allows
adjustment of the system ow rate to achieve the design ow rate.
As the exact total system pressure drop is not known upon
commissioning, it is necessary to adjust the water ow rate with the 
control valve to obtain the installation's specic ow rate.
8.3.2 - Hydraulic circuit cleaning procedure
Open the valve completely (item 22).
Start up the system pump.
Read the pressure drop of the plate heat exchanger using the
pressure di󰀨erential gauge to nd the di󰀨erence between the 
unit inlet and outlet (item 21).
Let the pump run for 2 hours continuously to ush the system's 
hydraulic circuit (presence of contaminating solids).
Perform another reading.
Compare this value to the initial value. A decrease in the
pressure  drop  value  indicates  that  the  lters  in  the  system
need to be removed and cleaned. In this case, close the Shut-
o󰀨 valves on the water inlet and outlet (item 19) and remove
then  clean  the  lters  (items  20  and  1)  after  draining  the
hydraulic part of the unit (item 6).
Remove the air from the circuit (items 5 and 17).
Repeat until all fouling is removed from the lter.
8.3.3 - Procedure for controlling the water ow
Once the circuit has been decontaminated, read the pressures on
the pressure gauges (water inlet pressure - outlet pressure) to
determine the pressure drop across the unit terminals (plate heat
exchanger + internal pipework).
Compare the value obtained with the theoretical selection value.
If  the  pressure  drop  reading  is  above  the  specied  value,  this 
indicates that the ow rate at the terminals of the unit (and hence 
in the system) is too high. In this case, close the control valve and
read the new di󰀨erence in pressure. Repeat as necessary until a 
specic pressure drop corresponding to  the unit's  nominal ow 
rate at the operation point is achieved.
NOTE: If the network has an excessive pressure drop in
relation to the available static pressure delivered by the
system pump, the nominal water ow rate cannot be obtained
(resulting ow rate is lower) and the di󰀨erence in temperature
between the water inlet and outlet of the evaporator will be
increased.
To reduce the system's hydraulic network pressure drop:
Reduce the pressure drops of individual components
(bends, level changes, valves etc.) as much as possible
• Use the correct pipe diameter;
• Avoid extending the hydraulic systems when possible.
8 - WATER CONNECTIONS
27

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier Aquasnap 30RB 160R and is the answer not in the manual?

Carrier Aquasnap 30RB 160R Specifications

General IconGeneral
BrandCarrier
ModelAquasnap 30RB 160R
CategoryChiller
LanguageEnglish

Related product manuals