Communication Guide, ©ComAp March 2014 124
IGS-NT Communication Guide 03-2014.pdf
Reset binary output RemoteSwitch1-8
(RemoteControl1-8 )
00100000
N/A
23,24,25,26
Set ExtValue1-4 (#2)
0002YYYY
(YYYY - new
value)
3
OK
1, 2
Not possible to perform
(*) in HEX
# 9
If the controller setpoints are not valid after it is switched on, the controller goes to a blocked state. In
this state it is necessary to modify the setpoints from the controller keypad and switch off and on the
controller or from the external terminal and unblock the controller by Reset from Init state command.
Another condition necessary to unblock the application function of the controller is valid configuration.
# 2
Check if the setpoints ExtValueXLoLim and ExtValueXHiLim allow set the requested value to
ExtValue.