Communication Guide, ©ComAp – March 2014 137
IGS-NT Communication Guide 03-2014.pdf
User & Password – in two steps
Request: 01 06 18 DA 00 00 AE 91
01 = controller address
06 = Modbus function code (Write Single Register)
18 DA = Register address: Object for user identification (46363) – 40001 = 6362 DEC
=> 18DA HEX
00 00 = ID of user; Administrator = 00 => 0000
91 AE = CRC (write LSB MSB !)
A part of dedicated communication objects table
Reserved (register not implemented)
User identification number (# 4)
Entering of password for writing (# 4)
Reserved (register not implemented)
Response: 01 06 18 DA 00 00 AE 91
01 = Controller address
06 = Modbus command
18 DA = Register addres
00 00 = Release value
91 AE = CRC
Request: 01 06 18 DB 00 00 FF 51
01 = controller address
06 = Modbus function code (Write Single Register)
18 DB = Register address: Object for entering password (46364) – 40001 = 6363 DEC
=> 18DB HEX
00 00 = Password = 00 => 0000
51 FF = CRC (write LSB MSB !)
Response: 01 06 18 DB 00 00 FF 51
01 = Controller address
06 = Modbus command
18 DB = Register addres
00 00 = Release value
51 FF = CRC
Hint:
Before entering the password for writing it is necessary to define user identification number. It is
recommended to enter user identification number and password simultaneously. Entered password
stays valid 5 minutes after the last successful writing.