Communication Guide, ©ComAp – March 2014 52
IGS-NT Communication Guide 03-2014.pdf
Active SMS
Function
When SMS active calls are activated for alarms on site (warning, shut-down…) the controller sends
SMS message to the predefined GSM number.
Controllers
Hint:
Active SMS uses for communication the modem connection.
Equipment
GSM Modem or I-LB + GSM Modem
Controller setup
(Setpoints/Comms settings group)
Act. Calls/SMS: AcallCH1(-3)-Type = SMS
Act. calls/SMS: AcallCH1(-3)-Addr = mobil phone number
Act. calls/Acall+SMS lang: AcallCH1(-3)-Addr = 1, 2, 3, ...
Hint:
Maximum length of SMS sent in not default language is 70 characters. Number of language
corresponds with number of language in GenConfig (card “Languages”).
Example
SMS in format
#Gen-set name:AL=(Wrn PrimWater temp, !Emergency stop)
is sent in case that the primary water temperature exceeded the warning limit and Emergency stop