EasyManuals Logo
Home>ComAp>Controller>InteliGen NTC

ComAp InteliGen NTC User Manual

ComAp InteliGen NTC
141 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Communication Guide, ©ComAp March 2014 52
IGS-NT Communication Guide 03-2014.pdf
Active SMS
Function
When SMS active calls are activated for alarms on site (warning, shut-down…) the controller sends
SMS message to the predefined GSM number.
Controllers
Controllers
IG-NTC-BB
IS-NTC-BB
IM-NTC-BB
Connection applicable
YES
YES
YES
Controllers
IG-NT
IG-NTC
IS-NT-BB
IM-NT
Connection applicable
YES
YES
YES
YES
Hint:
Active SMS uses for communication the modem connection.
Equipment
Equipment needed
Controller side
GSM Modem or I-LB + GSM Modem
Connection
GSM
PC side
GSM Mobile Phone
Controller setup
(Setpoints/Comms settings group)
Act. Calls/SMS: AcallCH1(-3)-Type = SMS
Act. calls/SMS: AcallCH1(-3)-Addr = mobil phone number
Act. calls/Acall+SMS lang: AcallCH1(-3)-Addr = 1, 2, 3, ...
Hint:
Maximum length of SMS sent in not default language is 70 characters. Number of language
corresponds with number of language in GenConfig (card “Languages”).
Example
SMS in format
#Gen-set name:AL=(Wrn PrimWater temp, !Emergency stop)
is sent in case that the primary water temperature exceeded the warning limit and Emergency stop
input has been deactivated.