Communication Guide, ©ComAp March 2014 33
IGS-NT Communication Guide 03-2014.pdf
Some devices do not support the modbus function 16. In this case can be the access code
writen in controller as one register No. 46339 using the function 6. The access code has to
be the number in the range 0 to 65535.
Equipment
Equipment needed
Controller side
-
Connection
Ethernet cable to LAN, for point to point connection
between PC and controller use cross-wired cable
PC side
ETHERNET connection
For more informations about ModBus implementation to ComAp controllers read the chapter ModBus
communication.
ModBus - Multiple gen-sets
RS485 MODBUS
Controllers
Controllers
IG-NTC-BB
IS-NTC-BB
IM-NTC-BB
Connection applicable
YES
YES
YES
Available ports
RS485(2)
RS485(2)
RS485(2)
Controllers
IG-NT
IG-NTC
IS-NT-BB
IM-NT
Connection applicable
NO
YES
YES
NO
Available ports
RS485(1)
RS485(1)
RS485(2)
RS485(2)
-
Controller setup
(Setpoints/Comms settings group)
RS232(2) mode = MODBUS-DIRECT
RS485(2) conv. = ENABLED
RS232(2)MBCSpd = 9600, 19200, 38400, 57600

Table of Contents