Communication Guide, ©ComAp March 2014 138
IGS-NT Communication Guide 03-2014.pdf
User & Password in one step
Request: 01 10 18 DA 00 02 04 00 00 00 00 D4 8C
01 = controller address
10 = Modbus command (Write Multiple Register)
18 DA = Register address: Object (46363) 40001 = 6362 DEC => 18DA HEX
00 02 = number of Modbus registers (user & password)
04 = data length in bytes (00 00 00 00)
00 00 00 00 = User identification “00 00” & password “00 00”
8C D4 = CRC (write LSB MSB !)
A part of dedicated communication objects table
Registers (*)
Register
addresses (*)
Number of
registers
Access
Data type
Meaning
46361
6360
1
write
Unsigned16
Command (# 3)
46362
6361
1
Reserved (register not implemented)
46363
6362
1
read/write
Unsigned8
User identification number (# 4)
46364
6363
1
write
Unsigned16
Entering of password for writing (# 4)
46365
6364
1
Reserved (register not implemented)
46366 46490
6365 6489
125
read
Domain
Values multipacket(#8)
Response: 01,10,18,DA,00,02,66,93
01 = Controller address
10 = Modbus command
18 DA = Register addres
00 02 = number of written Modbus registers
93 66 = CRC
Start the engine in one step
To start the engine it is necessary to enter an appropriate user and his password first to enable
commands, if these are protected by level 1-7.
Request: 01 10 18 D6 00 03 06 01 FE 00 00 00 01 95 53
01 = controller address
10 = Modbus command (Write Multiple Register)
18D6 = 6538 object for engine commands (46359) 40001 = 6358 DEC => 18D6 HEX
0003 = number of Modbus registers
06 = data length in bytes (01FE0000+0001)
01FE0000 = argument for Engine start (page 122)
0001 = command number (page 122)
53 95 = CRC (write LSB MSB !)
Response: 01 10 18 D6 00 03 67 50
01 = Controller address
10 = Modbus function code (Read Multiple Registers)
18 D6 = Register addres
00 03 = Release value, number of written Modbus registers
50 67 = CRC