Analog input item LiteEdit Possibility
Type Type Not used
Alarm
Analog input isn’t used
Analog input name Name Up to 14 ASCII characters
Config of input Config Analog
Binary (not supp. by PTM)
Tri-state (not supp. by PTM)
Analog measuring in specified
range.
Binary: open/close - threshold
750 Ω.
Three-state: open/close -
threshold 750 Ω,
Failure <10 Ω or > 2400 Ω
Physical dimension Dim bar,%,°C, … Up to 3 ASCII characters
(Valid only for analog inputs)
Polarity Contact
type
NC
NO
Valid only for binary and three-
state inputs
Valid only for binary and three-
state inputs
Over Overstep. Sensor fail does not
activate protection.
Over+Fls Overstep and Sensor fail
activates protection.
Under Under step. Sensor fail does
not activate protection.
Protection direction Protection
Under+Fls Under step and Sensor fail
activates protection.
Sensor characteristic Sensor Curve A
Curve B
Curve C
PT 1000
NI 1000
VDO Temp
VDO Press
VDO Level
4-20mA/100
4-20mA/ 60
Pt100
Ni100
0-20mA/100
4-20mA/100
0-100mV/100
iL, IOM,PTM
iL, IOM,PTM
iL, IOM,PTM
iL, IOM
iL, IOM
iL, IOM
iL, IOM,PTM
iL, IOM,PTM
iL, IOM
iL, IOM
PTM
PTM
PTM
PTM
PTM
User curve A
User curve B
User curve C
IEC 751, range -20 to 120 °C
DIN 43760, range -20 to 120
°C
See chapter sensor
specification
20mA/10.0Bar, ext. R 120 Ω
20mA/6.0Bar ext R 120 Ω
0-20mA/10.0Bar
4-20mA/10.0Bar
Decimal points Dec 0, 1, 2 Number of decimal points
(Valid only for analog inputs)
User Curve A, B, C are adjustable in LiteEdit.
Each Analog input has separate set points for two level alarm setting. Analog input alarm levels and
delay adjust in Protection or Engine protection group.
InteliLite – MRS10/11/15/16, SW version 2.2, ©ComAp – November 2004 15
IL-MRS-2.2.pdf