Technical data
Power supply
Voltage supply 8-36V DC
Consumption 0,5-0,1A depend on supply voltage
Allowed supply voltage drop-out: 50ms from min. 10V, return to min. 8V
(valid for InteliLite of hardware version 3.2 and higher)
Battery voltage measurement tolerance 2 % at 24V
Hint:
For the supply voltage less than 7V the backlight of the display is switched off.
Operating conditions
Operating temperature IL-CU -20..+70
o
C
Operating temperature IL-CU-LT
#
-30..+70
o
C
Storage temperature -30..+80
o
C
Protection front panel IP65
Humidity 95% without condensation
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
Vibration 5 - 25 Hz, ±1,6mm
25 - 100 Hz, a = 4 g
Shocks a = 200 m/s
2
#
Low Temperature modification
LCD display limits controller operating temperature range to –20
o
C - + 70
o
C even if the other
electronic components work in wider temperature range.
Internal preheating foil is mounted in InteliLite LT to extend display operational temperature range.
Preheating starts at temperature below 5
o
C and preheating power depends on temperature and
power supply voltage.
Technical data
IL-CU Standard Order code:IL-CU-LT
Operating temperature -20
o
C..+70
o
C -30
o
C..+70
o
C
Storage temperature -30
o
C..+80
o
C -30
o
C..+80
o
C
Preheating foil increases controller current consumption
Preheating at ambient temperature Controller
consumption at
No preheating
0
o
C -15
o
C -30
o
C
12VDC 360 mA +50 mA +180 mA +300 mA
24VDC 230 mA +25 mA +85 mA +150 mA
36VDC 100 mA +20 mA +65 mA +100 mA
InteliLite LT works immediately after switch on at -30
o
C and display becomes visible after a few
minutes.
InteliLite – MRS10/11/15/16, SW version 2.2, ©ComAp – November 2004 63
IL-MRS-2.2.pdf