Unction is active in any controller mode and activation of the input is written to history.
Remote man
If the input is active, MAN mode is forced to the controller independently on the position of the MODE
selector. If another of „remote“ inputs is active, then the Remote MAN input has the lowest priority.
Binary outputs IL-CU - default
BO1 Starter (relay output)
BO2 Fuel solenoid (relay output)
BO3 GCB Close/Open
BO4 Prestart
BO5 Ready to Load
BO6 Alarm
Binary outputs - list
Not used
Output has no function.
Starter
The closed relay energizes the starter motor.
The relay opens if:
the “firing” speed is reached or
maximum time of cranking is exceeded or
request to stop comes up
Fuel solenoid
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
Emergency stop comes or
Cooled gen-set is stopped or
in pause between repeated starts
Ignition
The output closes after reaching value of CrankRPM, fixed 30RPM. Opens after stopping of the
engine or in pause during repeated start.
Prestart
The output closes prior to the engine start (Prestart) and opens when START RPM speed is reached.
During repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Idle/Nominal
The output Idle/Nominal closes after the timer Idle time elapses. The Idle time counter starts to
countdown when Start speed reached. The Underspeed protection is not evaluated during idle period.
A Start fail protection occurs if the RPM drop below 2RPM during idle.
InteliLite – MRS10/11/15/16, SW version 2.2, ©ComAp – November 2004 22
IL-MRS-2.2.pdf

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS11 and is the answer not in the manual?

ComAp InteliLite MRS11 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS11
CategoryController
LanguageEnglish

Related product manuals