Alarm management
Following alarms are available:
Sensor fail
Warning
Shut down
Sensor fail (FLS)
Sensor fail is detected when measured value is 6% out of selected sensor characteristic. Sensor fail is
indicated by ##### symbol instead measured value.
Warning (WRN)
When warning comes up, only alarm outputs and common warning output are closed.
Possible warnings:
See List of possible events
Shut down (SD)
When the shut-down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL
SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and common
shutdown output are closed. Active or not reset protection disables start.
Possible shut-down alarms:
See List of possible events
Alarm time chart
"All the time" configured protections, I >, I >>, RPM >>, mains failure detection
GCB opened
"Engine running only" protections, engine
water temperature luboil pressure
Underspeed
Stop
Start
Starter OFF
Protection
delay
Switched to
nominal speed
Min stab time
GCB closed
Max stab time
Gen >U, <U, >f, <f
Idle time
InteliLite – MRS10/11/15/16, SW version 2.2, ©ComAp – November 2004 52
IL-MRS-2.2.pdf