appendIx
Daikin Applications
Parameter Settings:
The MD4 VFD has been made to Daikin specications. All
factory installed MD4 VFDs with MicroTech III controls are also
factory congured and started. Table 74 lists the parameters
that have been specically congured for Daikin or may need
owner adjustment as described in this manual.
• “HVAC Default” settings mentioned in the Table 74 note is
the vendor default if Parameter 9902 is set as shown.
• “Daikin Settings” are the recommended settings for Daikin
units.
• No other parameters should be needed or adjusted.
WARNING
Unintended Equipment Operation
• Modifying or changing parameters whose function is not
described in this manual will affect drive controller operation.
Some register changes will take effect as soon as they are
entered.
• Do not modify or change parameters whose function is not
described in this instruction bulletin.
Failure to follow this instruction can result in death, serious
injury, or equipment damage.
OM 1190-1 • MD4 VFD 108 www.DaikinApplied.com