Basic Operation Method
Characteristics of Dry Operation
In Dry operation, the air humidity will be lowered by intermittently
turning the air conditioner ON in cooling and OFF again to minimize
the temperature decrease.
Note
• The temperature and fan speed are controlled automatically and
cannot be controlled by the remote controller.
• Dry operation will not function if the room temperature is too low.
Setback
The Setback function will maintain the room temperature in a specic range when the remote
controller is turned OFF. This is done by temporarily starting the air conditioner that was previously
turned OFF by the user, the schedule function or the OFF timer.
OFF
Heating
Operation
Cooling Operation
10°C 12°C
33°C 35°C
For example:
[ Setback setpoint temperature: cool 35°C, heat 10°C ]
[ Recovery differential: cool -2°C, heat +2°C ]
• If the room temperature drops below 10°C, heating is started automatically. If after half an hour
the temperature increases to 12°C or above, the controller returns to its original state.
• If the room temperature goes above 35°C, cooling is started automatically. If after half an hour
the temperature drops to 33°C or below, the controller returns to its original state.
Note
• This function is disabled by default. This function can only be enabled/disabled in the Energy
Saving List (See "Energy Saving Options" on page 23).
• The differential can be adjusted in the Setback Condition menu (See "Setback Condition" on
page 25).
• The setback temperature can be set while the unit is turned off on the Basic Screen or set in the
schedule.
• Setback will turn the unit ON for at least 30 minutes unless the setback temperature setpoint is
changed or the unit is turned ON with the ON/OFF button.
• When setback turns the air conditioner ON while in Auto mode, the remote controller switches to
Cooling or Heating only, depending on what is appropriate, and only the respective setback
temperature setpoint is shown.
• The temperature is measured inside the air conditioner unit (when the unit is switched OFF). As
there is no actual air ow, the measured temperature inside the air conditioner unit can deviate
(up to 3°C) from the actual room temperature.