Troubleshooting for RA Indoor Unit Si18-525B
336 Troubleshooting
4.5 Shutter Drive Motor / Shutter Limit Switch Abnormality
Remote
Controller
Display
C7
Method of
Malfunction
Detection
The shutter open / close performance is detected by the limit switch attached on its structure. In
this way, the shutter drive motor and the shutter limit switch are checked for failure.
Malfunction
Decision
Conditions
When the shutter is open, the limit switch is closed.
Supposed
Causes
Shutter drive motor defective
Shutter limit switch defective
Shutter itself deformed (warped)
Shutter's sealing material too thick
Detection error by broken relay harness or disconnected connector
Detection error due to defective PCB (2)
Foreign substance in blow port
Troubleshooting
Check No.03
Refer to P.337
Turn off the power.
Check No. 03
Check the limit switch continuity.
Remove such substance.
Replace the limit switch.
Reconnect the connector or
replace the relay harness.
Replace the shutter drive
motor or the PCB (2).
Check the shutter's sealing
material.
Check the shutter for
deformation or its sealing
material.
(Q0410)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Foreign substance in
the shutter structure?
YES
NO
NO
NO
YES
Shutter closed?
NO
Shutter opening itself?
YES
YES
YES
NO
Relay harness
broken or connector
disconnected?
Limit switch on power?
Open the shutter and turn on the
power.

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Daikin D-Series and is the answer not in the manual?

Daikin D-Series Specifications

General IconGeneral
HSPF RatingUp to 10.0
Cooling Capacity9, 000 - 36, 000 BTU/h
Heating Capacity9, 000 - 36, 000 BTU/h
Energy Efficiency Ratio (EER)Up to 12.5
Sound Level19 - 50 dB (Indoor), 49 - 60 dB (Outdoor)
Noise Level19 - 50 dB (Indoor), 49 - 60 dB (Outdoor)
Power Supply208/230V, 1-phase, 60Hz

Summary

Part 2 Specifications

1. Specifications

Technical specifications for various models, including cooling and heating capacities.

1.1 Cooling Only

Detailed technical specifications for models in cooling-only mode.

1.2 Heat Pump

Detailed technical specifications for models in heat pump mode.

Part 3 Printed Circuit Board Connector Wiring Diagram

1. Printed Circuit Board Connector Wiring Diagram

Illustrates the wiring connections for PCBs in different unit types.

1.1 Outdoor Unit

Wiring diagrams for the outdoor unit's control and inverter PCBs.

1.1.1 Control PCB (A1P)

Lists connectors and their functions on the outdoor unit's control PCB.

Part 4 Refrigerant Circuit

Part 6 Test Operation

Part 8 Troubleshooting

1. Caution for Diagnosis

Important precautions and guidelines for diagnosing issues.

1.1 Troubleshooting with Operation Lamp

How to troubleshoot based on the status of the operation lamp.

1.2 Troubleshooting with the LED on the SkyAir Indoor Unit

Troubleshooting guide for LEDs on SkyAir indoor units.

1.3 Troubleshooting with the LED on the Outdoor Unit

Troubleshooting guide for LEDs on the outdoor unit.

1.4 Troubleshooting with the LED on the BP Unit

Troubleshooting guide for LEDs on the BP unit.

Related product manuals