Page #410 background imageLoading...
Page #410 background image
408
FTX-N/U, FVXS-N, FDMQ-R Series EDUS091558E
3P124623-1E
13
OPERATION MODE
The following five operation control modes can be selected along with the temperature setting and operation mode
by remote controller, for a total of twenty different modes. These twenty modes are set and displayed with control
modes of 0 to 19. (For further details, see EXAMPLE OF OPERATION SCHEDULE on the next page.)
ON/OFF control impossible by remote controller..... Use this mode when operating and stopping from the
central remote controller only. (ON/OFF control by the
remote controller is disabled.)
Only OFF control possible by remote controller ...... Use this mode when executing the operation only by the
central remote controller, and executing only the stop by
remote controller.
Centralized .............................................................. Use this mode when executing the operation only by the
central remote controller, and executing start/stop freely
by remote controller during the preset hours.
Individual ................................................................. Use this mode when executing start/stop both by central
remote controller and remote controller.
Timer operation possible by remote controller......... Use this mode when executing start/stop by remote con-
troller during the preset hours, and not starting operation
by the central remote controller at the programmed time
of system start.
[HOW TO SELECT THE CONTROL MODE]
Select whether to accept or to reject the operation from the remote controller regarding the operation, stop, tem-
perature setting and operation mode setting, respectively, and determine the particular control mode from the
rightmost column of the table below.
Example
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation by remote
controller (at time of
unified operation by
centralized control)
Operation
mode setting
by remote
controller
Temperature
control by
remote
controller
Stop by
remote
controller
[
Rejection
][
Rejection
][
Rejection
][
Acceptance
][
Acceptance
]
The control
mode is “ 1 ”.

Table of Contents

Other manuals for Daikin FDMQ-R Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FDMQ-R Series and is the answer not in the manual?

Daikin FDMQ-R Series Specifications

General IconGeneral
BrandDaikin
ModelFDMQ-R Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals