4-9
4.6 Refrigerant Recovery and Charge
Work Service port Notes
Operation
Pressure
cheek
High pressure
Low pressure
Refrigerant recovery & Recover all refrigerant from ports and .
Vacuum and dehydration & Vacuum and dehydrate from ports and .after recovering.
R134a
Refrigerant
charge
(Refer to note
1 of specified
charge amount
of refrigerant.)
(1) Liquid
charge
Charge liquid refrigerant from port after vacuum and
dehydration.
All specified charge amount of refrigerant can not be charged.
(2) Gaseous
charge
By operating unit, charge gaseous refrigerant from port for
the rest of specified charge amount of refrigerant.
Charging liquid refrigerant from port causes malfunction of
the compressor.
Note 1. Confirm specified charge amount of refrigeration indicated on model name plate.
The model name plate is mounted on the compressor chamber (behind of cable box).
EEV
HSV
LSV
DMV
LPT
CFM
①②
Compressor chamberValve chamber
0401-26LX10F11BEn.indd4-90401-26LX10F11BEn.indd4-9 2014/11/1916:42:132014/11/1916:42:13
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B and is the answer not in the manual?

Daikin LX10F11B Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B
CategoryInverter
LanguageEnglish

Related product manuals