EasyManuals Logo
Home>Daikin>Inverter>LX10F11B

Daikin LX10F11B User Manual

Daikin LX10F11B
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
1-3
1.2 Set Point and Protection Device
Component Name
Detector Symbol
Setting Value Alarm
High pressure switch HPS
OFF2400kPa24.47kg/cm
2
ON1900kPa19.37kg/cm
2
E101
F101
Pressure relief valve PRV Open2450kPa25.0kg/cm
2
)−
Fusible plug 95100℃(203212℉)
Built-in thermal protector
for condenser fan motor
Q1M
OFF135℃±5℃(275℉±41℉)
ON86℃±15℃(187℉±59℉)
Built-in thermal protector
for evaporator fan motor
OFF145℃±5℃(293℉±41℉)
ON94℃±15℃(201℉±59℉)
Circuit breaker (ELCB) CB 30A100mA)−
Fuse and Protection Circuit
Board Fuse Type Protection Circuit Alarm
I/O board
EC2
F1U
F10A 250V
fast-acting type
I/O board control powerDC13.5V, 5V, 3.3V
F2U
PCC1, PCC2, CFH, CFL, EFH, EFL
HSV, RSV, LSV, ESV
F703
F707
E115
E117
F3U Spare
PT/CT
board
EC7
F11U 8A 600V PT/CT board control power
Noise filter
board
EC9
F5U
12.5A 300A
Surge absorber 1 (lightning surge protection)
<Non-replaceable>
F6U
Surge absorber 2 (lightning surge protection)
<Non-replaceable>
F7U
Surge absorber 3 (lightning surge protection)
<Non-replaceable>
F8U 8A 600V Inverter control circuit <Non-replaceable>
I/O board
EC2
TH3
2.5A 72V
Automatic reset
RM (Remote Monitoring) circuit
<Non-replaceable>
TH2 TransFresh circuit <Non-replaceable>
0101-22LX10F11BEn.indd1-30101-22LX10F11BEn.indd1-3 2014/11/1916:40:192014/11/1916:40:19
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B and is the answer not in the manual?

Daikin LX10F11B Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B
CategoryInverter
LanguageEnglish

Related product manuals