EasyManuals Logo
Home>Daikin>Inverter>LX10F11B

Daikin LX10F11B User Manual

Daikin LX10F11B
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #120 background imageLoading...
Page #120 background image
5-2
5.1 Standard Tightening Torque for Bolt and Flare Nut
Type Size
Tightening Torque
Example of Application
Nm kgfm lbfft
Bolt
M4 1.6 16 1.2 Small parts
M5 3.0 30 2.3
Solenoid valve
Inverter box cover
M6 5.2 51 3.8
Slide plate for EFM stator
Condenser fan grille
Solenoid valve chamber cover
M8 12.3 121 9.1
Fixing plate of evaporator fan diffuser
Condenser fan motor
Control box door
Access panel
M10 25.2 247 18.6
M12 42.7 418 31.5 Compressor base
M14
Reverse threaded
67.8 664 50.0 Evaporator fan shaft
Flare nut
φ6.4, 1/4 15.7 154 11.6 Low-pressure port
φ9.5, 3/8 36.3 356 26.8
φ12.7, 1/2 54.9 538 40.5 Dryer, Compressor injection port
Compressor
connector
(φ19.1 , 3/4
122 1200 90 Compressor suction and discharge
0501-08LX10F11BEn.indd5-20501-08LX10F11BEn.indd5-2 2014/11/1916:41:472014/11/1916:41:47
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B and is the answer not in the manual?

Daikin LX10F11B Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B
CategoryInverter
LanguageEnglish

Related product manuals