ST9702-1 type USDA Sensor Characteristics, USDA1, USDA2, USDA3,
CTS (Option)
Set sensor type "1" in 12 Configuration Set
in paragraph 2.3 for ST9702-1 type USDA
sensor.
       
Temperature
(℃)
Temperature
(󱌞F
Resistance
kΩ)
Temperature
(℃)
Temperature
(󱌞F
Resistance
kΩ)
20 4 36.240 10 50 9.196
19 2 34.470 11 52 8.821
18 0 32.800 12 54 8.465
17 1 31.220 13 55 8.124
16 3 29.720 14 57 7.800
15 5 28.310 15 59 7.490
14 7 26.970 16 61 7.194
13 9 25.710 17 63 6.911
12 10 24.510 18 64 6.641
11 12 23.370 19 66 6.383
10 14 22.290 20 68 6.136
9 16 21.270 21 70 5.901
8 18 20.300 22 72 5.675
7 19 19.380 23 73 6.460
6 21 18.510 24 75 5.253
5 23 17.680 25 77 5.056
4 25 16.900 26 79 4.867
3 27 16.150 27 81 4.685
2 28 15.440 28 82 4.513
1 30 14.770 29 84 4.348
0 32 14.120 30 86 4.189
1 34 13.520 31 88 4.036
2 36 12.940 32 90 3.891
3 37 12.380 33 91 3.751
4 39 11.860 34 93 3.617
5 41 11.360 35 95 3.488
6 43 10.880 36 97 3.365
7 45 10.430 37 99 3.247
8 46 9.999 38 100 3.133
9 48 9.588 39 102 3.024
10 50 9.196 40 104 2.919
AD970217A
Receptacle for
ST9702-1
setting "1"
0501-08LX10F11BEn.indd5-60501-08LX10F11BEn.indd5-6 2014/11/1916:41:502014/11/1916:41:50
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B and is the answer not in the manual?

Daikin LX10F11B Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B
CategoryInverter
LanguageEnglish

Related product manuals