4-15
4.8.2 Replacing the evaporator fan motor
1Removing
aRemove access panel.
bLoosen 4 pcs bolts (M8) from fan blade fixing metal.
c Disconnect power supply connector on
fan motor.
dPull the fan assembly straight out.
e Remove fan diffuser and replace fan motor.
(The screw of fan fixing nut (M14) is reverse direction.)
2Installation
f Re-stall fan in a reverse way of removing.
(Securely connect the power supply connector for the fan motor.
Tighter Looser
Loosen the four M8 bolts.
0401-26LX10F11BEn.indd4-150401-26LX10F11BEn.indd4-15 2014/11/1916:42:202014/11/1916:42:20