2-9
2-6 ACT, Automatic Cold Treatment
When cold treatment is completed during USDA transport,
this ACT function switches the temperature to the preset
temperature automatically. (See paragraph 1.5.3 for the detail.)
Step 1. Press or key to select either "ON" or "OFF".
ON To enable automatic change of setting temperature
OFF To disable automatic change of setting temperature
Step 2. When selecting "ON" and determining by pressing
key, the previous setting screen appears (Fig. 1).
The following four settings are required.
1. USDA CT days (1 to 99 days)
2. USDA Max. Temperature (-4.9 to 30.0 )
3. USDA SetpointSP (-4.9 to 30.0 )
4. Final-SP (-4.9 to 30.0 ) after USDA CT
Step 3. ACT setting procedure: See the case example below.
CT 10 days
USDA Max. 1.0
Setpoint 0.0
Final-SP 3.0
3-1. Set CT to 10 days.
Press key to change the previous CT to "10" days,
the first SP, and press
key to determine. (Fig. 2)
3-2. Press key to move to next setting item USDA Max, then
press key, scroll with keys until USDA Max turns
to "1.0" and press key to determine. (Fig. 3)
3-3. Similarly, set Setpoint to "0.0" and Final-SP to "3.0" .
(Fig. 3)
Step 4. Finally, press key to start ACT operation. (Fig. 4)
2-7 G-set set
It is able to select power consumption limit of the unit in order to continuous operation as much as
possible when power supply is not enough capacity.
1. Press key to select total
power consumption and press
key to determine.
OFF, 11, 12, 13,
14 or 15kVA
When a G-set setting has been made, the total power consumption will take priority, so that refrigeration
performance may be insufficient under some conditions.
2-8Fan Speed Control
1. Press key to select "OFF"
or "ON", and press key to
determine.
AUTO During chilled operation, the evaporator fan runs at high speed/low speed.
High Spd During chilled operation, the evaporator fan runs at high speed.
Automatic Cold Treatment
OFF
USDA Max 2.0 C
Setpoint 1.0 C
Final SP 5.0 C
Automatic Cold Treatment
CT Days 15Day
Fig. 1
Previous setting screen
Fig. 2
Fig. 3
Fig. 4
Press
Enter to Start
ESC to Cancel
Automatic Cold Treatment
USDA Max 2.0 C
Setpoint 1.0 C
Final SP 5.0 C
Automatic Cold Treatment
CT Days 10Day
Setpoint 0.0 C
Automatic Cold Treatment
CT Days 10Day
USDA Max 1.0 C
Final SP 3.0 C
▲▼ : Change
ENTER : Confirm
▲▼ : Change
ENTER : Confirm
▲▼ : Change
ENTER : Confirm
▲▼ : Change
ENTER : Confirm
G-SET
▲▼ : Change
ENTER : Confirm
▲▼ : Change
ENTER : Confirm
OFF
13kVA
G-SET
▲▼:Change
ENTER:Confirm
▲▼:Change
ENTER:Confirm
AUTO
High Spd
Fan Speed Control
Fan Speed Control
0201-18LX10F11BEn.indd2-90201-18LX10F11BEn.indd2-9 2014/11/1916:38:402014/11/1916:38:40
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B and is the answer not in the manual?

Daikin LX10F11B Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B
CategoryInverter
LanguageEnglish

Related product manuals