Si04-306 Problem Symptoms and Measures
Service Diagnosis 91
2. Problem Symptoms and Measures
Symptom Check Item Details of Measure Reference
Page
None of the units operates. Check the power supply. Check to make sure that the rated voltage is
supplied.
Check the type of the indoor units. Check to make sure that the indoor unit type is
compatible with the outdoor unit.
Check the outdoor air temperature. Heating operation cannot be used when the
outdoor air temperature is 24°C or higher (only
for heat pump model), and cooling operation
cannot be used when the outside temperature
is below 5°C (10°C for Europe).
Diagnosis with remote controller
indication
93
Check the remote controller
addresses.
Check to make sure that address settings for
the remote controller and indoor unit are
correct.
Operation sometimes
stops.
Check the power supply. A power failure of 2 to 10 cycles can stop air
conditioner operation. (Operation lamp OFF)
Check the outdoor air temperature. Heating operation cannot be used when the
outdoor air temperature is 24°C or higher (only
for heat pump model), and cooling operation
cannot be used when the outside temperature
is below 5°C (10°C for Europe).
Diagnosis with remote controller
indication
93
Equipment operates but
does not cool, or does not
heat (only for heat pump
model).
Check for wiring and piping errors in
the indoor and outdoor units
connection wires and pipes.
Conduct the wiring/piping error check described
on the product diagnosis nameplate.
Check for thermistor detection errors. Check to make sure that the main units
thermistor has not dismounted from the pipe
holder.
Check for faulty operation of the
electronic expansion valve.
Set the units to cooling operation, and compare
the temperatures of the liquid side connection
pipes of the connection section among rooms to
check the opening and closing operation of the
electronic expansion valves of the individual
units.
Diagnosis with remote controller
indication
93
Diagnosis by service port pressure
and operating current
Check for insufficient gas. 131
Large operating noise and
vibrations
Check the output voltage of the
power transistor.
132
Check the power transistor. ——
Check the installation condition. Check to make sure that the required spaces
for installation (specified in the Technical
Guide, etc.) are provided.

Table of Contents

Other manuals for Daikin RXS50BVMA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RXS50BVMA and is the answer not in the manual?

Daikin RXS50BVMA Specifications

General IconGeneral
BrandDaikin
ModelRXS50BVMA
CategoryAir Conditioner
LanguageEnglish

Related product manuals