Troubleshooting Si04-306
122 Service Diagnosis
4.20 Low-voltage Detection
Remote
Controller
Display
U2
Method of
Malfunction
Detection
An abnormal voltage rise or drop is detected by checking the detection circuit or DC voltage
detection circuit.
Malfunction
Decision
Conditions
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer, or
the voltage being detected by the DC voltage detection circuit is judged to be below 150 V
for 0.1 second.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 60 minutes (normal)
Supposed
Causes
Supply voltage not as specified
Over-voltage detector or DC voltage detection circuit defective
PAM control part(s) defective
Troubleshooting
Check the supply voltage.
Correct the power supply.
Check for such factors for a
long term.
Try to get restarted a
couple of times.
Replace the SPM.
(Replace the outdoor unit
PCB.)
(R2854)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Supply voltage as
specified?
NO
YES
Turn on the
power again.
System restarted?
NO
Repeat a
couple of times.
YES
(Precaution before turning on the power again)
Make sure the power has been off for
at least 30 seconds.
Disturbance factors
Noise Power supply distortion

Table of Contents

Other manuals for Daikin RXS50BVMA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RXS50BVMA and is the answer not in the manual?

Daikin RXS50BVMA Specifications

General IconGeneral
BrandDaikin
ModelRXS50BVMA
CategoryAir Conditioner
LanguageEnglish

Related product manuals