Troubleshooting by Indication on the Remote Controller
115
3.27
E6
STD Compressor Motor
Overcurrent/Lock
Remote Controller Display
E6
Applicable Models
VRVII, III and III-Q Series
Method of Error Detection
Detects the overcurrent with current sensor.
Error Decision Conditions
Error is decided when the detected current value
exceeds the below mentioned value for 2 seconds.
Supposed Causes
Stop valve is not opened
Obstacles at the air outlet
Improper power voltage
Defective magnetic switch
Defective compressor
Defective current sensor