EasyManuals Logo

Daikin VRVII User Manual

Daikin VRVII
385 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #264 background imageLoading...
Page #264 background image
Troubleshooting by Indication on the Remote Controller
259
3.59
U1
Reverse Phase, Open
Phase
Remote Controller Display
U1
Applicable Models
VRVII, III, -WII, -WIII and III-Q Series
Method of Error Detection
The phase of each phase are detected by reverse phase
detection circuit and right phase or reverse phase are
judged.
Error Decision Conditions
When a power supply is reverse phase, or T phase is
open phase.
Supposed Causes
Power supply reverse phase
Power supply open phase
Defective outdoor (outside) unit PCB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRVII and is the answer not in the manual?

Daikin VRVII Specifications

General IconGeneral
BrandDaikin
ModelVRVII
CategoryAir Conditioner
LanguageEnglish

Related product manuals