Troubleshooting by Indication on the Remote Controller
162
3.36
J1
High Pressure Sensor
Abnormality
Remote Controller Display
J1
Applicable Models
VRVIII-Q Series
Method of Error Detection
Error is detected from the pressure measured with high
pressure sensor.
Error Decision Conditions
When the high pressure sensor is short-circuit or open
circuit.
Supposed Causes
Defective high pressure sensor
Connection of low pressure sensor with wrong
connection.
Defective outdoor unit PCB.
Defective connection of high pressure sensor