Troubleshooting by Indication on the Remote Controller
365
List of inverter-related error codes
Code Name
Condition for
determining error
Major cause
Compressor current
L5 Instantaneous
overcurrent of
inverter
compressor
Inverter output current
exceeds 32.3A even
instantaneously.
Liquid sealing
Defective
compressor
Defective inverter
PCB
L8 Overcurrent of
inverter
compressor
(Electronic
thermal)
Compressor overload
running
An overcurrent of
19.0A or more
continues for a period
of 5 consecutive
seconds or that of
16.1A or more
continues for a period
of 260 consecutive
seconds.
For 230V units:
A current of 33.5A or
more continues for a
period of consecutive
5 sec. or that of 27.6A
or more continues for
a period of
consecutive 260 sec.
The inverter loses
synchronization.
Back-flow of
compressor liquid
Sudden changes
in loads
Disconnected
compressor
wiring
Defective inverter
PCB
CHECK 9