EasyManuals Logo

Daikin VRVII User Manual

Daikin VRVII
385 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #170 background imageLoading...
Page #170 background image
Troubleshooting by Indication on the Remote Controller
165
3.37
J2
Current Sensor
Abnormality
Remote Controller Display
J2
Applicable Models
VRVIII and III-Q Series
Method of Error Detection
Error is detected according to the current value detected
by current sensor.
Error Decision Conditions
When the current value detected by current sensor
becomes 5A or lower, or 40A or more during standard
compressor operation.
Supposed Causes
Defective current sensor
Defective outdoor unit PCB
Defective compressor