Appendix A. Specifications
EI.65.D4.02
115
APPENDIX A. SPECIFICATIONS
A.1 General Data
Supply voltage 230 V version:
24 V version:
230 V AC 50 Hz
24 V AC 50 Hz
Power Consumption 5 VA
Voltage range 230 V version:
24 V version:
207 – 244 V AC
21.6 – 26.4 V AC
Cable Max. 1.5 mm
2
Ambient temperature
0 50 °C
Storage temperature
– 40 70 °C
Enclosure 144 x 96 mm DIN 43700
EMC Radiation Complies with: Emission: EN50081-1
Immunity: EN50082-1
Protection class According to installation:
IP 41 DIN 40050 together with 087B8099
IP 65 DIN 40050 together with 087B3064
Sensor type
Pt 1000 (1000 at 0 °C)
Fast digital input 1 fast digital input:
2 fast digital inputs:
3 fast digital inputs:
4 fast digital inputs:
0 200 Hz
0 100 Hz
0 66.7 Hz
0 50 Hz
Voltage input
0 10 V DC
Load on 3-point outputs 230 V version:
24 V version:
0.15 A
1 A
Load on relay outputs 230 V version:
24 V version:
4 (2) A 230 V AC
4 (2) A 24 V AC
Power backup of real-time clock 3 years
Accuracy of real-time clock
± 15 s/year

Table of Contents

Other manuals for Danfoss ECL 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL 2000 and is the answer not in the manual?

Danfoss ECL 2000 Specifications

General IconGeneral
BrandDanfoss
ModelECL 2000
CategoryTemperature Controller
LanguageEnglish

Related product manuals