Application 11
EI.65.D4.02
84
6.3.12 Application 11
System diagram 11A
Two separate heat circuits with common primary heat exchanger for a heat circuit
and a hot-water circuit with indirect control.
Heat circuit 1 The motor valve M1 controls the flow temperature, which is measured by the sen-
sor S1. The return temperature measured by the sensor S2 can be limited. The cir-
culation pump P1 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
Heat circuit 2 The motor valve M2 controls the flow temperature, which is measured by the sen-
sor S4. The return temperature measured by the sensor S5 can be limited. The cir-
culation pump P2 is running when the reference flow temperature is above 20 °C
or when the outdoor temperature is below 2 °C.
Hot-water circuit The hot-water circuit is connected to the secondary side of the heat exchanger, in
parallel with heat circuit 2. The charging pump P3 performs on/off control of the
storage tank temperature, which is measured by the sensor S6. Service-water
heating takes priority over room heating, i.e. the circulation pump P2 in heat cir-
cuit 2 is stopped during tank charging. The pump P4 maintains circulation through
the storage tank but is not controlled by the ECL 2000.

Table of Contents

Other manuals for Danfoss ECL 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL 2000 and is the answer not in the manual?

Danfoss ECL 2000 Specifications

General IconGeneral
BrandDanfoss
ModelECL 2000
CategoryTemperature Controller
LanguageEnglish

Related product manuals