EasyManuals Logo
Home>Danfoss>Temperature Controller>ECL 2000

Danfoss ECL 2000 Installation Guide

Danfoss ECL 2000
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
Application 5
EI.65.D4.02
57
6.3.6 Application 5
System diagram 5A
Heat circuit and hot-water circuit with indirect control of storage tank.
Heat circuit The motor valve M1 controls the flow temperature, which is measured by the sen-
sor S1. The return temperature measured by the sensor S2 can be limited. The cir-
culation pump P1 is running when the reference flow temperature is above 20 °C
or the outdoor temperature is below 2 °C.
Hot-water circuit The motor valve M2 controls the charging temperature, which is measured by the
sensor S4. The upper and lower storage tank temperatures are measured by the
sensors S6 and S7, respectively. A low S6 temperature causes the charging pump
P2 to start and the pump is stopped when a high temperature is measured at S7. It
is possible to limit the return temperature measured by S5. The circulation pump
P3 is controlled according to the 7-day program.

Table of Contents

Other manuals for Danfoss ECL 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL 2000 and is the answer not in the manual?

Danfoss ECL 2000 Specifications

General IconGeneral
BrandDanfoss
ModelECL 2000
CategoryTemperature Controller
LanguageEnglish

Related product manuals