Mounting
EI.65.D4.02
7
3.2 Panel Mounting
For panel mounting you must use a cutout of 92 x 138 mm. The maximum sheet
thickness of the front plate is 3 mm (see Figure 7).
1. Fit four retainer springs on the controller before mounting.
The retainer springs are available as accessories (code no. 087B3076).
This set consists of four springs and two terminal blocks.
2. Make the electrical connections to the loose terminal blocks.
3. Insert the controller into the panel cutout (see Figure 7).
Figure 7. Panel mounting
4. Fit the terminal blocks to the connectors on the controller’s rear side as
shown in Figure 8.
The terminal blocks are coded to prevent mains voltage section from be-
ing connected to low-voltage section.
Figure 8. Fastening terminal blocks to the controller’s rear