Application 10
EI.65.D4.02
83
Wiring Type 2
Input Type 2
Name Pin Common Description
S1 3 12 Flow temperature, heat circuit 1. Must be connected
S2 4 12 Return temperature, heat circuit 1
S3 5 12 Outdoor temperature. Must be connected
S4 6 12 Flow temperature, heat circuit 2. Must be connected
S5 7 12 Return temperature, heat circuit 2
S6 8 12 Hot-water temperature. Must be connected
S7 9 12 Optional: Can be installed to measure lower storage tank
temperature
S8 10 12 Default: Room temperature, heat circuit 1. Can be rede-
fined
S9 11 12 Default: Room temperature, heat circuit 2. Can be rede-
fined
S10 23 12 Available
S11 24 12 Return temperature, hot-water circuit. Must be connected
Output Type 2
Name Pin Neutral Description
P1 16 13 Circulation pump, heat circuit 1
P2 17 13 Circulation pump, heat circuit 2
P3 18 13 Circulation pump, hot-water circuit. Can be redefined
M1 19 12 Motor valve on primary side, heat circuit 1
M2 20 12 Motor valve on primary side, heat circuit 2
M3 21 12 Motor valve on primary side, hot-water circuit

Table of Contents

Other manuals for Danfoss ECL 2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL 2000 and is the answer not in the manual?

Danfoss ECL 2000 Specifications

General IconGeneral
BrandDanfoss
ModelECL 2000
CategoryTemperature Controller
LanguageEnglish

Related product manuals