Application 10
EI.65.D4.02
82
Output Type 1
Name Pin Neutral Description
P1 18 13 Circulation pump, heat circuit 1
P2 19 13 Circulation pump, heat circuit 2
M
(ON/OFF)
20 13 Motor valve on primary side of hot-water circuit. This ac-
tuator must be of a type that opens/closes upon receiving a
relay signal from the controller
M1 16, 17 13 Appl. 10A: Motor valve on primary side, heat circuit 1
16: Close. 17: Open
Appl. 10B: Mixing valve in heat circuit 1
16: Reduce temperature. 17: Increase temperature
M2 23, 24 13 Appl. 10A: Motor valve on primary side, heat circuit 2
23: Close. 24: Open
Appl. 10B: Mixing valve in heat circuit 2
23: Reduce temperature. 24: Increase temperature