Application 12
EI.65.D4.02
92
Wiring Type 2
Input Type 2
Name Pin Common Description
S1 3 12 Water temperature on secondary side of common heat ex-
changer. Flow temperature, heat circuit 1. Must be con-
nected
S2 4 12 Return temperature
S3 5 12 Outdoor temperature (heat circuit 1). Must be connected
S4 6 12 Flow temperature, heat circuit 2. Must be connected
S5 7 12 Return temperature, heat circuit 2
S6 8 12 Optional: Outdoor temperature, heat circuit 2
S8 10 12 Default: Room temperature, heat circuit 1. Can be rede-
fined
S9 11 12 Default: Room temperature, heat circuit 2. Can be rede-
fined
S10 23 12 Available
S11 24 12 Available
Output Type 2
Name Pin Neutral Description
P1 16 13 Circulation pump, heat circuit 1
P2 17 13 Circulation pump, heat circuit 2
P3 18 13 Available
M1 19 12 Motor valve on primary side of common heat exchanger
M2 20 12 Mixing valve in heat circuit 2