1 Limit for heating cut-out
Circuit Setting range Factory setting
I 10 ... 30 °C 20 °C
Set the outdoor temperature limit at which you
want the heating system to stop.
The valve closes and after about 3 min. the heating
circulation pump stops.
The min. limitation set in line 2 will be ignored.
Temp.
Actual Accumulated
outdoor temp. outdoor temp.
Heating OFF
Time
Heating Heating
This function can save energy by stopping the heating system
when the outdoor temperature gets above a set limit. The heating
system switches ON again when the outdoor temperature and
the accumulated outdoor temperature become lower than the set
limit.
When the limit value is set to 30, there is no heating cut-out.
Heating cut-out is active when the controller mode is scheduled
operation.
Heating cut-out -
line 1
21