The grey
side of the
ECL Card
Extended service
32a
Service parameter(s) 10-11
10 Choice of room panel / remote control
Circuit Setting range Factory setting
I 1 ... 8 5
Decides the communication with the room panel or remote
control.
Please note that the room panel / remote control is only active
if the system device bus is active. The bus is active when the
outdoor temperature sensor is connected.
Choose between
1: Room panel ECA 60 / 62 or remote control
ECA 61 / 63 with address A
2: Room panel ECA 60 / 62 or remote control
ECA 61 / 63 with address B
3 ... 4: Not used
5: No room panel or remote control
6 ... 8: Not used
The room panel / remote control has no influence on the DHW
control.
11 Setback temperature dependent on outdoor
temperature
Circuit Setting range Factory setting
(I) / (II) OFF / -29 ... 10 °C (-15) / (-15) °C
Below this outdoor temperature, the setback temperature setting
has no influence.
-29 ... 10:
The setback temperature depends on the
outdoor temperature, when the outdoor
temperature is above the set limit. The
lower the outdoor temperature, the less the
temperature reduction. When the outdoor
temperature is below the set limit, there is
no temperature reduction.
OFF: The setback temperature does not depend
on the outdoor temperature.
100%
0%
-20 -10-29 0 20
10
Reduction
Outdoor
temperature
°C
Setting line 11