Control & overviews
ECL Card settings
(circuit II)
30b
A Time and date Section 17
B System information Sections 18 & 19
C Storage tank sensor(s)
Section 20
Setting ranges Factory settings Your settings
1
Cut-out temperature difference
1 ... 99 K 15 K
See section 27
2
Cut-in temperature difference
1 ... 99 K 20 K
See section 27
3
4
Proportional band, Xp
1 ... 250 K 80 K
See section 26
5
Integration time constant, Tn
5 ... 999 sec. 30 sec.
See section 26
6
Running time of the motorized control
valve
5 ... 250 sec. 35 sec.
See section 26
7
Neutral zone, Nz
0 ... 9 K 3 K
See section 26