78 Desired temperature for anti-bacteria function
Circuit Setting range Factory setting
II OFF / 1 ... 100 °C OFF
Set the desired temperature for the anti-bacteria function.
The DHW will be charged once a week at the set temperature
to protect against bacteria. The function is always active on
Mondays from 00:00 and the DHW is charged according to the
period set in line 80.
OFF: The anti-bacteria function is not active.
1 ... 100:
The anti-bacteria function is active at the
desired temperature.
80 Anti-bacteria function period
Circuit Setting range Factory setting
(I) / (II) 5 ... 250 min. 120 min.
Set the period for the anti-bacteria function. When the set time
expires, the anti-bacteria function is stopped.
5 ... 250:
The anti-bacteria function is active for the
set period.
The function is activated in line 78 by setting the desired anti-
bacteria temperature.
83 Internal relationship between circuits I and II
Circuit Setting range Factory setting
II 0 ... 4
0
State which circuit in the controller has the leading temperature
control. The table below will help you make the choice.
The configuration of the master / slave controllers in the network
is carried out in line 199.
State the controller's role in relation to heating
system type.
Heating
system type
(section 10)
Stand-alone
controller
Master
controller
Slave
controller
1 and 4
4 4 4
2, 2a, 3, 6 and 6a
0 3 0 (1)
5 2 2 2
For the heating system types 1, 4 and 5 as well as in the master
controller, the value set in line 17 must be within the range 1-20.
For heating system types 2, 2a, 3, 6 and 6a setting ‘1’ is only
necessary if circuit I has the leading temperature control.
This setting is only seldomly used.