FC 300 Design Guide
How to Program
" Parameters: DeviceNet
CAN Fieldbus
" 10-0* Common Settings
10-00 CAN Protocol
Option:
*
DeviceNet [1]
Function:
Selection of CAN protocol.
10-01 Baud Rate Select
Option:
*
125 Kbps [20]
250 Kbps [21]
500 Kbps [22]
Function:
Selection of the DeviceNet transmission sp ee d. The
selection must correspond to the transmission sp eed
of the master and the other DeviceNet nodes.
10-02 MAC ID
Option:
0 - 127 N/A
*
63 N/A
Function:
Selection of station add ress. Every station
connected to the same DeviceNet network must
have an unambiguous address.
10-05 Readout Transmit Error Counter
Range:
0-255
*
0
Function:
A readout of the Transmit Error C ounter of the
CAN controller since the last power-up.
10-06 Readout Receive Error Counter
Range:
0-255
*
0
Function:
Displays the Receive Error Counter of the CAN
controller since the last power-up.
10-07 Readout Bus Off Counter
Range:
0 - 10 00
*
0
Function:
Displays the number of Bus Off events
since the last power-up.
" 10-1* DeviceNet
10-10 Process Data Type Selection
Option:
Instance 100/150 [0]
Instance 101/151 [1]
Instance 20/70 [2]
Instance 21/71 [3]
Function:
Permits selection of 6 d ifferent Instances for data
transmission. Instances 100/150 and 10 1/1 51 are
Danfoss-specific. Instance 20/70, 2 1/71, 22/72,
and 23/73 are ODVA-specific AC Drive profiles.
A change to this pa rameter is not executed
until the next power-up.
10-11 Process Data Config Write
Option:
None [0]
Minimum reference par. 3-02
Maximum reference par. 3-03
Catch up/slow do wn value par. 3-12
Ramp 1 ramp up time par. 3-41
Ramp 1 ramp down time par. 3-42
Ramp 2 ramp up time par. 3-51
Ramp 2 ramp down time par. 3-52
Jogramptimepar. 3-80
Quick stop ramp time par. 3-81
Motor speed low lim it par. 4-11 [RPM]
Motor sp eed hi gh limit par. 4-13 [RPM]
Torque limit motor m ode par. 4-16
Torque limit generator mode par. 4-17
Bus Jog 1 Speed par. 8-90
Bus Jog 2 Speed par. 8-91
Fieldbus CTW 1 par. 16-8 0
Fieldbus REF 1 par. 16-82
Function:
Used for the pre-defined I /O assembly Insta nces.
Only 2 elem ents [1,2] of this array are used. All
elements are set to 0 as default.
10-12 Process Data Config Read
Option:
None [10]
*
default setting ()display text []value for use in communication via serial communication port
192
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals