FC 300 Design Guide
Introduction to FC 300
EMC Test Results (Emission, Immunity)
The following test results have been obtained using a system with an adjustable frequency drive (with options if relevant), a shielded control cable,
a control box with potentiometer, as well as a motor and motor cable.
FC 301/FC 302 Conducted emission Radiated emission
200-240 V
380-500 V
Environment Industrial environment Housing, trades
and light
industries
Industrial
environment
Housing, trades
and light
industries
Basic standard
Setup Motor cable
EN 55011 Class
A2
EN 55011 Class
A1
EN 55011
Class B
EN 55011 Class
A1
EN 55011 Class B
FC 301/FC 302 A2
0-5 HP (0-3.7 kW) 200-240 V
0-10 HP (0-7.5 kW) 380-500 V
16 ft (5 m) shielded/ar-
mored
Yes No No No No
33 ft (10 m)
shielded/armored
Yes Yes Yes Yes No
131 ft (40 m)
shielded/armored
Yes Yes No Yes No
FC 301 with integrated filter
0-5 HP (0-3.7 kW) 200-240 V
0-10 HP (0-7.5 kW) 380-500 V
492 ft (150 m)
non-shielded/unarmored
No No No No No
131 ft (40 m)
shielded/armored
Yes Yes Yes Yes No
492(150m)
shielded/armored
Yes Yes No Yes No
FC 302 with integrated filter
0-5 HP (0-3.7 kW) 200-240 V
0-10 HP (0-7.5 kW) 380-500 V
984 ft (300 m)
non-shielded/unarmored
No No No No No
45
MG.33.B3.22 - VLT is a registered Danfoss trademark