FC 300 Design Guide
How to Program
Bit 04, ON 2/OFF 2
Bit 04 = "0": Bit 01 of t he Control word is "0". Bit 04 = " 1": Bit 01 of the Control word is "1".
B
it 05, ON 3/OFF 3
Bit 05 = "0": Bit 02 of t he Control word is "0". Bit 05 = " 1": Bit 02 of the Control word is "1".
B
it 06, Start possible/Start not possible
Bit 06 is always "0" if FC Drive in par. 8-10 is sele cted. Selecting PROFIdrive in par. 8-10 ,
bit 06 is "1" after a switch-off a ckno wle dgement, after activation of OFF2 or OFF3, and after
switching o n mains voltage. Start is not possible. The adjustable frequency drive is reset with
bit 00 of the Control word set to "0" and bit 01, 02, and 10 set to "1".
B
it 07, No warning/Warning
Bit 07 = "0": No unusual situation. Bit 07 = "1": There is an unusual status in the adjustable frequency
drive. For more information about warnings - see the FC 300 Profibus Operating Instructions.
B
it 08, Speed ≠reference / Spe ed = reference:
Bit 08 = "0": The motor speed deviates from the set speed reference value. This occurs
e.g. when the speed is changed during start/stop through ramp-up/down. Bit 08 = "1": The
motor speed corresponds to the set spe ed reference value.
B
it 09, Local operation/Bus control
Bit 09 = "0": Indicates that the adjustable frequency d rive is stopped via [Stop] o
r that Local is selected in
par. 0-02. Bit 09 = "1": The adjustable frequency drive is controlled through the serial interface.
B
it 10, Out of frequency limit/Frequency limit OK
Bit 10 = "0": The output frequency is outside the limits set in par. 4-11 and par. 4-13 (Warnings: Motor
speed low or high limit). Bit 10 = "1": T he output frequency is w ithin t
he indicated limits.
B
it 11, No operation/Operation
Bit 11 = "0": The motor is not running. Bit 11 = "1": A start signal is active or
the output f re quency is higher than 0 Hz.
B
it 12, Drive OK/Stopped, autostart
Bit 12 = "0": No temporary overloading of the inverter. Bit 12
= "1": The inverter stops due to overload. How-
ever, t he adjustable frequency drive is not switched off (tri pped) and wi ll restart after the overloading stops.
B
it 13, Voltage OK/Voltage exceeded
Bit 13 = "0": The adjustable frequency drive voltage limits are not exceeded . Bit 13 = "1": The
direct voltage in the drive intermediate circuit is t
oo low or too high.
B
it 14, Torque OK/Torque exceeded
Bit 14 = "0": The motor current is below the m oment limit selected in par. 4-18. Bit 14
= "1": The torque limit selected in par. 4-18 is exceeded .
B
it 15, Timer OK/Timer exceeded
Bit 15 = "0": The timers for the therma l motor pro
tection and adjustable frequency drive thermal protection
have not exceeded 100%. Bit 15 = "1": One of the tim ers has exceeded 100%.
*
default setting ()display text []value for use in communication via serial c ommunication port
252