3.4.6 Process PID Control
The process PID control can be used to control application parameters that can be measured by different sensors (pressure,
temperature, and flow) and be affected by the connected motor through a pump or fan.
Table 3.9 shows the control configurations where the process control is possible. When a flux vector motor control principle
is used, the speed control PID parameters should also be tuned. Refer to chapter 3.2.2 Control Structure in VVC
plus
Advanced
Vector Control to see where the speed control is active.
1-00 Configuration Mode 1-01 Motor Control Principle
U/f
VVC
plus
Flux Sensorless Flux w/enc. feedb
[3] Process N.A. Process Process & Speed Process & Speed
Table 3.9 Process Control Configurations
NOTICE!
The process control PID works under the default parameter setting, but tuning the parameters is highly recommended
to optimize the application control performance. The two flux motor control principles are particularly dependent on
proper speed control PID tuning to yield their full potential. The speed control PID tuning occurs before tuning the
process control PID.
Figure 3.22 Process PID Control Diagram
Product Introduction Design Guide
MG34S222 Danfoss A/S © Rev. 2014-02-10 All rights reserved. 41
3 3

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300
CategoryDC Drives
LanguageEnglish

Related product manuals